Catalog

Featured Products

Product's News

Contact Information
| HDR-120 |


| Bookmark This Page | ||||||
| Print This Page | ||||||
| Live Messenger | ||||||
| Skype Me | ||||||
| Peter@greegoo.com | ||||||
| Catalogue Download | ||||||
| Add to Inquiry Basket | View Inquiry Basket | ||||||
| Industrial DIN Rail Power Supplies(120W Single Output) |
|---|
| - Universal AC input / full range - Protections: Short circuit/ Over load/ Over voltage/Over temperature - Cooling by free air convection - Can be installed on DIN rail TS-35/7.5 or 15 - LED indicator for power on - 100% full load burn-in test - Fixed switch frequency at 55KHz - 3 years warranty - Dimensions: 65.5*125.2*100mm (W*H*D) |
| Model | HDR-120-12 | HDR-120-24 | HDR-120-48 | |
| Output | DC Voltage | 12V | 24V | 48V |
| Voltage Tolerance | +2% | +1% | +1% | |
| Rated Current | 10A | 5A | 2.5A | |
| Current Range | 76W | 76.8W | 76.8W | |
| Rated Power | 0-10A | 0-10A | 0-2.5A | |
| Ripple & Noise | 80mVp-p | 80mVp-p | 100mVp-p | |
| DC Adjustment Range | 12-14V | 24-28V | 48-53V | |
| Setup, Rise, Hold Time | 500ms,70ms/230VAC at full load500ms,70ms/115VA Cat full load | |||
| Hold Time | 36ms/230VAC32ms/115VAC at full load | |||
| Input | Voltage Range | 88~132 VAC/176~264VAC47~63 Hz;selected by 248~370VDC | ||
| AC Current | 2.6 A/115 V 1.6A/ 230 V | |||
| Efficiency | 80% | 84% | 85% | |
| Inrush Current | Cold start 20A/115V 40A/230V | |||
| Leakage Current | <3.5mA/240VAC | |||
| Protection | Over Load | 105%~150% | ||
| Protection type: Constant current limiting, recovers automatically after fault condition is removed | ||||
| Over Voltage | 120%~135% | |||
| Protection type: Shut down o/p voltage, re-power on to recover | ||||
| OVER TEMP. | 85℃+5℃(TSW1) | 90℃+5℃(TSW1) | 90℃+5℃(TSW1) | |
| Protection type: Shut down o/p voltage, recovers automatically after temperature goes down |
||||
| Environment | Working Temp & Humidity | -10℃~+60℃;20%~90 %RH | ||
| Storage Temp &Humidity | -20℃~+85℃;10%~95 %RH | |||
| Vibration | 10~500Hz,2G 10min./1cycle, period for 60min, each along X, Y, Z axes | |||
| Safety | Withstand Voltage | I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC | ||
| Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG: 100MΩ / 500VDC | |||
| Standards | Safety Standard | Design refer to UL508,UL60950-1,TUV EN60950-1 | ||
| EMC Standard | Design refer to EN55011,EN55022,EN61000-3-2,-3, EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2 | |||
| Others | Weight | 0.79Kg | ||
| Packing | 20pcs/16.5Kg/1.1CUFT | |||
If you would like a quotation or further information on this product, please fill in the form below and we will reply to you within 1 working day. |
Related Products: