Catalog

Featured Products

Product's News

Contact Information
| HDR-75 |


| Bookmark This Page | ||||||
| Print This Page | ||||||
| Live Messenger | ||||||
| Skype Me | ||||||
| Peter@greegoo.com | ||||||
| Catalogue Download | ||||||
| Add to Inquiry Basket | View Inquiry Basket | ||||||
| Industrial DIN Rail Power Supply(75W Single Output) |
|---|
| - Universal AC input/ full range - Protections: Short circuit/ Over load/ Over voltage/Over temperature - Cooling by free air convection - Can be installed on DIN rail TS-35/7.5 or 15 - LED indicator for power on - 100% full load burn-in test - Fixed switching frequency at 50KHz - 3 years warranty - Dimensions: 55.5*125.2*100mm (W*H*D) |
| Model | HDR-75-12 | HDR-75-24 | HDR-75-48 | |
| Output | DC Voltage | 12V | 24V | 48V |
| Voltage Tolerance | +2% | +1% | +1% | |
| Rated Current | 6.3A | 3.2A | 1.6A | |
| Current Range | 76W | 76.8W | 76.8W | |
| Rated Power | 32.5W | 54W | 60W | |
| Ripple & Noise | 100mVp-p | 150mVp-p | 240mVp-p | |
| DC Adjustment Range | 17% | 17% | 10% | |
| Setup, Rise, Hold Time | 1000ms,60ms/230VAC at full load1800ms,60ms/115VACat full load | |||
| Hold Time | 60ms/230VAC 12ms/115VAC at full load | |||
| Input | Voltage Range | 85~264 VACselected by switch 47~63 Hz;120~370VDC | ||
| AC Current | 1.6 A/115 V 0.96A/ 230 V | |||
| Efficiency | 76% | 80% | 81% | |
| Inrush Current | Cold start 20A/115V 40A/230V | |||
| Leakage Current | <1mA/240VAC | |||
| Protection | Over Load | 105%~160% | ||
| Protection type: Constant current limiting, recovers automatically after fault condition is removed | ||||
| Over Voltage | 120%~140% | |||
| Protection type: Hiccup mode, recovers automatically after fault condition is removed |
||||
| OVER TEMP. | TSW1≥85℃+5℃ | |||
| Protection type: Shut down o/p voltage, recovers automatically after temperature goes down | ||||
| Environment | Working Temp & Humidity | 10℃~+60℃;20%~90 %RH | ||
| Storage Temp &Humidity | -20℃~+85℃;10%~95 %RH | |||
| Vibration | 10~500Hz,2G 10min./1cycle, period for 60min, each along X, Y, Z axes | |||
| Safety | Withstand Voltage | I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC | ||
| Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG: 100MΩ / 500VDC | |||
| Standards | Safety Standard | Design refer to UL508,TUV EN60950-1 | ||
| EMC Standard | EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 | |||
| Others | Weight | 0.6Kg | ||
| Packing | 20pcs/13Kg/1.1CUFT | |||
If you would like a quotation or further information on this product, please fill in the form below and we will reply to you within 1 working day. |
Related Products: